Rockwell Automation MAO04NND Analogue Output Module User Manual
Page 4

4
MAO04NND Octrober 2005 – Issue 1
Triguard SC300E
SPECIFICATION
Model
MAO04NND
Channels
4
Architecutre
TMR
Indicators
Health, 3 x On Line
Test points
4 x signal, 1 x common
Output range
0 to 22mA
Maximum resistive field load
400 ohm
Resolution
6.25
µA steps
Accuracy @ 25
°
C
+
0.2% of full signal range
Maximum input ripple voltage @ 24V field supply
12V peak to peak
Maximum input frequency
120HZ
Stability (temperature coefficient)
15ppm/
°
C
Isolation
1KV between field and system, commoned
supply
Field power supply
Volgate range
+18Vdc to 30Vdc
Module power consumption
5.5W
Overall size (mm)
Overall size (inches)
400(9U)H x 397L x 28W
15.75H x 15.63L x 1.1W
Weight
1.4kg
ENVIRONMENTAL SPECIFICATIONS
The maximum ambient temperature measured at the hottest point within the Triguard system
shall not be greater than 60 degrees centigrade.
Temperature operating:
+5°C to +60°C
Temperature storage:
-25°C to +70°C
Humidity
5% to 95% non-condensing at ambient <40°C
EMC/RFI Immunity
Tested and certified to IEC 1131-Part 2 1994
Vibration/Shock
Tested and certified to IEC 1131-Part 2 1994
Certification:
General Certification: Ref. SC300E TMR Product Guide (ref 008-5209).