Rockwell Automation LiquiFlo 2.0 Switch Mode Power Supply Replacement User Manual

Rockwell Automation Equipment

Advertising
background image

LiquiFlo is a trademark of Rockwell Automation.

©2004 Rockwell Automation. All rights reserved.

LiquiFlo 2.0 Power Interface and Switch Mode Power Supply

Replacement Instructions

Instruction Manual D2-3512-1

Replacing the Power Interface Assembly

!

ATTENTION: Retain the insulation sheet when removing the old Power Supply assembly. The
insulation sheet must be installed between the Power Interface assembly and the new Power
Supply assembly. Failure to follow this precaution could result in damage to, or destruction of,
the equipment.

2

3

Install (or re-use) the 3 plastic spacers (P/N 179773).

Carefully align and press the Power Interface Assembly onto the plastic spacers until fastened.

Fasten (and ground) the Power Interface Assembly to the Control Panel
using the five screws (P/N 179103-Q05). Torque = 0.6 to 0.7 N-m (5 to 6 in/lb).

1

Insulation sheet
(Glued to Control Panel)

Control Panel

1

1

2

3

3

Power Interface
Assembly

Advertising