Rockwell Automation T8832 Trusted 60 Channel Analogue Input FTA User Manual

Sds-8832, Trusted, Industrial control system trusted

Advertising
background image

SDS-8832

Trusted

TM

Industrial Control System

Trusted

TM

60 Channel Analogue Input FTA - T8832

Issue 5 Jan 2006

GENERAL ASSEMBLY

DESCRIPTION


The Trusted

TM

Field Termination Assembly (FTA) Analogue Input 60-

Channel is designed to act as the main interface between a field device
generating a digital signal and the Trusted

TM

Dual Analogue Input Module

T8432.

The field supply is derived from dual 24V dc feeds, which are ‘commoned’
via diodes on the FTA. The supply is then fed to each channel. Channel 0
on the Trusted

TM

Dual Analogue Input Module will be configured in the

future to provide monitoring of the field power supply.

The supply voltage to the field is fed via a 50mA fuse. The incoming signal
from the field device is developed across a 250R resistor, then connected to
the appropriate input circuit on the Input Module. Line monitoring
components (if required) provide the necessary thresholds used by the input
module to detect the field loop/device status, i.e. open/short circuit, alarm
etc.

The cable linking the 60 channels on the input module to the FTA is
terminated at a 96-way socket. The dual dc power supplies are connected
to the FTA via a single 4-way connector. Ten 12-way connectors are used
for the field loops.

The FTA is designed to be mounted on either of the TS32 or TS35 DIN rails
in the horizontal or vertical positions as required.

FEATURES

Sixty input channels per
FTA

Industry standard field
device connections (2-wire)

Standard DIN rail
compatibility

Simple installation and
connection

24V dc operation

Fused field power supply
per channel