Block diagram, Single channel schematic, Electrical specification – Rockwell Automation T8832 Trusted 60 Channel Analogue Input FTA User Manual

Page 2: Sds-8832 trusted, Industrial control system trusted

Advertising
background image

SDS-8832
Trusted

TM

Industrial Control System

Trusted

TM

60 Channel Analogue Input FTA - T8832

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

BLOCK DIAGRAM

Single Channel Schematic

ELECTRICAL SPECIFICATION

Field Supply Range

0 to 140V dc

Fuses

61-off 50mA

Maximum Current (Field Supply)

3A

Recommended Operating Current

0 to 20mA per channel

Power Consumption (Field Supply)

6.5W maximum

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
110mm x 455mm x 68mm
(4.3ins x 17.9ins x 2.6ins)

Weight (fully populated)
762gms
(1.68lbs)

ENVIRONMENTAL


Operating Temperature:

-5

°C to 60°C

(23

°F to 140°F)


Operating Humidity:
5 to 95%, non-
condensing

Vibration:
10 to 57Hz

±0.075mm

57 to 150Hz 1.0g

Shock:
15g, ½ sine wave, 11ms

EMI (IEC 801):
ESD
Air discharge to 15kV.
Contact discharge to 8kV

Radiated Fields
10V/m, 27MHz to
500MHz

Transients and Bursts
2kV, 2.5kHz for
t=60 seconds

Advertising