Rockwell Automation T8403 Trusted 24V dc Digital input Module - 40 Channel User Manual

Page 18

Advertising
background image

Trusted

TM

Module T8403

Issue 15 Jun 13

PD-T8403

18

Value

Description

7

Unknown

5

Short circuit

4

Closed contact

3

Indeterminate

2

Open contact

1

Open circuit

Table 7 Rack 2: STATE Output descriptions

The input channel has a value 7 (Unknown) when:

1. The input channel cannot be correctly measured by two or more slices of the TMR input

module.

2. The TMR Processor detects a 2oo3 channel discrepancy between the three slices of the

TMR input module.

3. The module is simulated (not installed or the TMR Processor cannot communicate with 2oo3

slices of the module).

3.2.3. Rack 3: AI

The AI board returns the field loop voltage at the input.

Channel

Description

1

Field input channel 1 voltage

2

Field input channel 2 voltage

40

Field input channel 40 voltage

Table 8 Rack 3: Channel Field Voltage

The voltage is the median value taken from the triplicated module. The voltage level is reported as an
integer, with the units being

1

/

512

V. This may be used directly, scaled arithmetically or scaled using the

IEC1131 TOOLSET conversion tables.

When used directly the value may be considered as a signed, fixed-point binary value, i.e.:

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Sign

Integer

Fractional

Table 9 Rack 3: Channel Field Voltage bit definitions

To scale the value arithmetically, simply divide the input value by 512 to return the voltage as either a
REAL or INTEGER as required.

The IEC1131 TOOLSET conversion tables may be used to convert the input value to engineering
units, in this case voltage. The full-scale range for this number format is decimal ±64, corresponding
to physical range –32768 to +32767. Other units may be chosen depending on the numeric resolution
and span of the desired result.