Rockwell Automation T8293 Trusted Power Distribution Unit 15-Way Fused User Manual
Sds-8293 trusted, Industrial control system trusted
 
SDS-8293 
Trusted
TM
Industrial Control System
Trusted
TM
Power Distribution Unit 15-Way Fused-T8293
Issue 5 Jan 2006
GENERAL ASSEMBLY
DESCRIPTION
 
The Trusted
TM
Power Distribution
Unit 15-way Fused provides 15 
dual redundant fused power 
outputs from dual redundant 24V 
dc or 48V dc incoming power 
feeders. The Unit is designed to 
be mounted on a DIN rail. 
On-board
monitoring
circuits
provide local LED indication of 
individual fuse failure (red LED). 
A common fuse failure alarm 
signal is provided by the Unit via 
a volt-free relay contact output. 
Two 24V dc or 48V dc (link 
selectable) 
supplies,
are
distributed through 30 fuses, 
arranged in two banks of 15 
fuses. The outputs are fed via 15 
terminal blocks labelled T1 to T7, 
and T11 to T18. 
Each supply shares a common 
0V reference. 
A volt-free relay contact provides 
the fuse failure common alarm 
signal (contact open for fuse 
failure) for connection to external 
alarm monitoring circuits. 
FEATURES
Fifteen ‘dual’ 24V dc or 48V 
dc, 3A fuse protected 
outputs – suitable for direct 
connection to Trusted
TM
Field Termination 
Assemblies (FTAs), or other 
equipment 
Visual indications of input 
power supply status 
Visual indication of 
individual fuse status 
Common alarm of fuse 
status via volt-free contact 
Link-selectable supply 
voltage options