Block diagram, Electrical specification, Sds-8293 trusted – Rockwell Automation T8293 Trusted Power Distribution Unit 15-Way Fused User Manual

Page 2: Industrial control system trusted

Advertising
background image

SDS-8293
Trusted

TM

Industrial Control System

Trusted

TM

Power Distribution Unit 15-Way Fused-T8293

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

BLOCK DIAGRAM

ELECTRICAL SPECIFICATION

Voltage Range

22-30V dc or 43-60V dc (link selectable)

Supply Current

23A maximum

Supply Connection

LU10.16 screw clamp terminal

Supply Conductor Clamping
Range -

solid

stranded

AWG Conductors

0.5 to 16mm

2

0.5 to 10mm

2

No. 22…8

Input Power Supply Indication

2-off green LEDs

Output Indication

30-off red LEDs indicating individual
failed fuses

Fused Outputs

30 arranged in two banks of 15

Fuse Type

3A 5x20mm cartridge

Leakage Current (failed fuse)

0.6mA @ 30V dc or 1.2mA @ 60V dc
maximum

Output Connector

BLZ 2-part terminal

Output Conductor Clamping
Range

0.5 to 2.5mm

2

AWG Conductors 28...14

Common Alarm Output

Volt-free contact – powered, closed in
healthy state

Maximum Switching Voltage

60V dc or 125V ac @ 0.5A

Minimum Load

5V @ 1mA

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
79mm x 285mm x 109mm
(3.1ins x 11.2ins x 4.3ins)

Weight:
576g
(1.3lbs)

ENVIRONMENTAL


Operating Temperature:

-5

°C to 60°C

(23

°F to 140°F)


Operating Humidity:
5 to 95%, non-condensing

Vibration:
10 to 57Hz

±0.075mm

57 to 150Hz 1.0g

Shock:
15g, ½ sine wave, 11ms

EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV

Radiated Fields
10V/m, 27MHz to
500MHz

Transients and Bursts
2kV, 2.5kHz for
t=60 seconds