Rockwell Automation T8480 Trusted TMR Analogue Output Module User Manual

Sds-8480 trusted, Industrial control system trusted, Tmr analogue output module-t8480

Advertising
background image

SDS-8480
Trusted

TM

Industrial Control System

Trusted

TM

TMR Analogue Output Module-T8480

Issue 7 Sep 2006

FRONT PANEL

DESCRIPTION


The Trusted

TM

TMR Analogue Output

module interfaces to 40 field output
devices. Outputs are arranged in five
groups of eight outputs. All outputs in
a group share a common power
source and return. Fault tolerance is
achieved through Triple Modular
Redundancy (TMR) within the same
module for each of the 40 output
channels.

The module provides on-board
Sequence of Events (SOE) reporting
with a resolution of 1ms. The “event”
is the actual sensing of the field
device loop current. Each triplicated
section (slice) of the module receives
output data from the Trusted

TM

TMR

Processor and sends its data to an
internal safety layer hardware voter.

Each slice uses the voted data to
control the outputs. Every output
channel consists of a six-element
voted array. The output switch array
provides fault tolerant, uninterrupted
control under an output switch failure
condition. Output switching and fault
diagnostics

comply

with

the

demanding requirements of IEC-
61508 SIL-3 for First Fault - Fault
Tolerant, and Second Fault - Fail
Safe outputs.

When a module fault is detected, the
Trusted

TM

TMR Processor will flag the

unhealthy condition, indicating the
need to replace the module. Control
continues

until

a

replacement

(healthy)

module

is

available.

Replacement modules can be located
in a standby slot next to the module
or in a designated SmartSlot with a
temporary connection to the same
Trusted

TM

Termination Assembly.

Each output is user configurable to
perform line monitoring of the
connected field devices to detect field
wiring and load failures. Automatic
over-current protection is inherent in
every output circuit which eliminates
the need for fuses.

Modules may be placed in any I/O
module slot in a Trusted

TM

Processor

Chassis or Expander chassis. Once
the I/O module configuration is set,
mechanical keying is available on all
I/O modules to prevent inserting a
module into an incorrect slot.

Configuration of the module is carried
out using the Trusted

TM

Toolset

running

on

an

Engineering

Workstation. Once configured and
loaded into the Trusted

TM

Controller,

replacement modules are on-line
educated by the TMR Processor.

FEATURES

40 TMR output channels per
module

Five isolated groups of eight
outputs each

Six-element voted output array

Comprehensive diagnostics
and self-test

Guaranteed, First fault – Fault
Tolerant, Second fault – Fail
Safe

Line monitoring on a per
channel basis

Automatic over-current
protection – no fuses required

2500V dc Opto-Isolation

Hot replaceable

Front panel status LEDs for
each channel

Module fault and status
indicators

IEC 61508, SIL 3 safety
applications

On-board 1 ms resolution
Sequence of Events reporting

Advertising