Block diagram, Electrical specification, Sds-8480 trusted – Rockwell Automation T8480 Trusted TMR Analogue Output Module User Manual

Page 2: Industrial control system trusted, Tmr analogue output module-t8480, Ics triplex, Mechanical specification, Environmental, Ofiu hiu fpdu fpiu, Oftu

Advertising
background image

SDS-8480
Trusted

TM

Industrial Control System

Trusted

TM

TMR Analogue Output Module-T8480

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

BLOCK DIAGRAM

ELECTRICAL SPECIFICATION

Number of Outputs

40 Channels

No. of Independent Power Groups

5, each of 8outputs

Field Common Isolation

Sustained Working

±250V dc

Maximum Withstanding

±2.5kV dc

Output Current

Range

0.33-22mA

Output Current Rating

Continuous

22mA

Output Off Resistance (effective
leakage)

69k=

Step Response (10-90%)

10ms

Circuit Type

Fault tolerant, fully triplicated with
optional line monitoring

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
241mm x 30mm x 300mm
(9.5ins x 1.2ins x 11.8ins)

Weight:
1.13kg
(2.5lbs)

ENVIRONMENTAL


Operating Temperature:

-5

°C to 60°C

(23

°F to 140°F)


Operating Humidity:
5 to 95%, non-
condensing

Vibration:
10 to 57Hz

±0.075mm

57 to 150Hz 1.0g

Shock:
15g, ½ sine wave, 11ms

EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV

Radiated Fields
10V/m, 27MHz to
500MHz

Transients and Bursts
2kV, 2.5kHz for
t=60 seconds

Slice Power

Supply

Housekeeping

Failsafe Bias Control

A

Back Plane

Power Bus

1

Front Panel

T

M

R

In

te

rm

o

d

u

le

B

u

s

Opto Isolation Boundary

Serial Display Latches

Voted Status Display LEDs

Internal Voting Bus

Housekeeping

Module Temp

Supply Diag

DSP reference

Health

Indicators

Back Plane Power Bus 1

Back Plane Power Bus 2

Slice A

OFIU

HIU

FPDU

FPIU

Field Logic

Control

Redundant Supply

N.C.

N.O.

Diagnostic

Monitor

Bus

Interface

Bus

Interface

Slice Power

Supply

Housekeeping

Failsafe Bias Control

B

Field Logic

Control

N.C.

N.O.

Diagnostic

Monitor

Slice Power

Supply

Housekeeping

Failsafe Bias Control

C

Field Logic

Control

N.C.

N.O.

Diagnostic

Monitor

Bus

Interface

Front Panel

Voting Logic

Slice

Control

B

Time Stamp

Slice

Control

B

Time Stamp

Slice

Control

A

Time Stamp

OFTU

+V

Slice B

Slice C

A

B

C

Group

Fail-Safe

Switch

-

V

Field Interface

Protection Circuit

Advertising