(T3404) AC Digital Input Module


P D - 6 0 1 3 M a r - 0 6

15

Specifications

Safetybus Power

1.15 load units

Number of Inputs

16 circuits divided into two
groups of eight

Voltage Range

90 to 130 VAC

Frequency Range

47 to 63 Hz

Turn-On Voltage

89 VAC, minimum

Turn-Off Voltage

30 VAC, maximum

Input Current

3.9 mA, typical

Turn-On Delay

minimum

maximum

3.5 msec

20 msec

Turn-Off Delay

minimum

maximum

3.5 msec
15 msec

Over Voltage Protection

continuous:

burst:


160 VAC
260 VAC, for 5 sec

Heat Dissipation

14 Watts, 48 BTUs/hour

Fusing

None, fuse external if
required

Isolation

2500 volts minimum (field
wiring to control logic)
2500 volts minimum (input
group 1-8 to input group
9-16)

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Storage Temperature

-40

°

to 85

°

C

(-40

°

to 185

°

F)

Operating Humidity

0 to 95% relative humidity,
non-condensing

Vibration

10 to 55 Hz:


±0.15mm