Specifications – Rockwell Automation T3404 ICS Regent AC Digital Input Module 110 VAC User Manual
Page 15

(T3404) AC Digital Input Module
P D - 6 0 1 3 M a r - 0 6
15
Specifications
Safetybus Power
1.15 load units
Number of Inputs
16 circuits divided into two
groups of eight
Voltage Range
90 to 130 VAC
Frequency Range
47 to 63 Hz
Turn-On Voltage
89 VAC, minimum
Turn-Off Voltage
30 VAC, maximum
Input Current
3.9 mA, typical
Turn-On Delay
minimum
maximum
3.5 msec
20 msec
Turn-Off Delay
minimum
maximum
3.5 msec
15 msec
Over Voltage Protection
continuous:
burst:
160 VAC
260 VAC, for 5 sec
Heat Dissipation
14 Watts, 48 BTUs/hour
Fusing
None, fuse external if
required
Isolation
2500 volts minimum (field
wiring to control logic)
2500 volts minimum (input
group 1-8 to input group
9-16)
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity,
non-condensing
Vibration
10 to 55 Hz:
±0.15mm