Module – mbb (bus interface module), Trusted™ bridge module 8161, 2 module – mbb (bus interface module) – Rockwell Automation SC300E Trusted Bridge Module User Manual

Page 18

Advertising
background image

Trusted™ Bridge Module 8161

Issue 2 Feb 10

PD-8161

18

3.2.2 Module – MBB (Bus interface Module)

DESCRIPTION
This definition provides module status for a logical Triguard MBB local chassis expansion module.
The logical module accounts for the 3 physical modules FCR-A, FCR-B and FCR-C.

OEM PARAMETERS:

OEM parameter

Valid numbers

Description


CHASSIS

2-29

Logical chassis number allocated to the local
secondary Triguard chassis in which the MBB
modules are placed.


SLOT

15

Logical slot within the local secondary Triguard
chassis by which the 8000 system identifies the
MBB module. This cannot be configured.


PHYSICAL MODULE:

RACK 1: [STATUS] - 10 BOOL Inputs

Variable 1:

FALSE (Not used)

Variable 2:

TRUE = FCR-A faulted

Variable 3:

TRUE = FCR-B faulted

Variable 4:

TRUE = FCR-C faulted

Note: The status of MBB FCR's can only be determined by the discrepancy status of accesses

performed to I/O modules within the chassis of the MBB. If no such modules exist or if no MBB
FCR's are fitted then no faults can be reported.

Advertising