Module – mai32lad (0-5v; analogue input module), Trusted™ bridge module 8161 – Rockwell Automation SC300E Trusted Bridge Module User Manual

Page 19

Advertising
background image

Trusted™ Bridge Module 8161

Issue 2 Feb 10

PD-8161

19

3.2.3 Module – mai32lad (0-5V; analogue input Module)

DESCRIPTION
This definition will open a single MAI32LAD.

OEM PARAMETERS

OEM parameter

Valid numbers

Description


CHASSIS

2-29

Logical chassis and slot number where the

SLOT

1-10

MAI32LAD is located.


PHYSICAL MODULE:

RACK 1: (AI)

32 INTEGER inputs


RACK 2: (DIAG)

3 INTEGER inputs

Word 1 Health status bits, 0=healthy 1=fault

bit 0-2

Microcontroller watchdog (bit 0=A, bit 1=B, bit2=C)

bit 3-5

MP watchdog (bit 0=A, bit 1=B, bit2=C)

bit 6-8

Microcontroller slice health (bit 0=A, bit 1=B, bit2=C)

bit 9-11

Combined slice health (bit 0=A, bit 1=B, bit2=C)

bit 12

Power Fail

bit 13-15

not used

Word 2 Diagnostic bits

bit 0

Slice A

=1

slice is not responding or there is an error

=0

slice is responding

bit 1

Slice B

=1

slice is not responding or there is an error

=0

slice is responding

bit 2

Slice C

=1

slice is not responding or there is an error

=0

slice is responding

bit 3

Module offline or missing

=1

offline or missing

=0

online

bit 4

Single slot hot repair

=1

in progress

=0

not in progress

bit 5

Discrepancy errors

=1

faults detected

=0

no faults detected

bit 6

LFD faults

=1

faults detected

=0

no faults detected

Word 3 Slot number of active module


RACK 3: (FAULTS)

4 INTEGER inputs

Word 1

Discrepancy errors, channels 1-16 (bit 0 = channel 1)

Word 2

Discrepancy errors, channels 17-32 (bit 0 = channel 17)

Word 3

LFD errors, channels 1-16 (bit 0 = channel 1)

Word 4

LFD errors, channels 17-32 (bit 0 = channel 17)

Advertising