Network Status (NS)
Off
Module is not online.
• Module is autobauding.
• No power applied to the module;
look at Module Status LED.
Flashing Red
One or more I/O connections are in the
timed-out state.
Solid Red
Failed communications (duplicate MAC ID
or bus-off).
Flashing Green
Module is online but no connections are
currently established.
Solid Green
Module is online with connections
currently established.
Channel 0 &
Channel 1
Off
• Normal operation within alarm limits
on the channel.
• No power applied to the module; look
at the Module Status LED.
Solid Yellow
Alarm associated with this channel is in
Alert.
Solid Red
Alarm associated with this channel is in
Danger.
Flashing Red
A transducer fault exists on the channel.
DC bias is outside the DC Low and High
Limits.
Tachometer
Off
• Normal operation within alarm limits
on the channel.
• No power applied to the module; look
at the Module Status LED.
Solid Yellow
Alarm on Speed or Acceleration is in
Alert.
Solid Red
Alarm on Speed or Acceleration is in
Danger.