Fault/fail connectors (j2 & j3), Diagnostic connector (j4), Psu shutdown monitor connector (j6) – Rockwell Automation T812X Trusted Processor Interface Adaptor User Manual

Page 9: Trusted, Process interface adaptor t812x

Advertising
background image

Trusted

TM

Process Interface Adaptor T812X

Issue 8 Sep 07

PD-T812X

9

1.2. Fault/Fail Connectors (J2 & J3)

J2 and J16 are Phoenix contact 2.5mm pitch connectors.

Pin

Service

1

FAULT_n_NC

2

FAULT_n_COMMON

3

FAULT_n_NO

4

FAIL_n_NC

5

FAIL_n_COMMON

6

FAIL_n_NO

Table 2 Fault/Fail Connectors

Note: n=1 for connector J2 and 2 for connector J3 providing fault and fail connections for the Active

and Standby processors respectively. FAULT opens on any system fault which sets the
Processor Healthy LED red. FAIL opens on shutdown of the Processor.

1.3. Diagnostic Connector (J4)

J4 is a Phoenix contact 2.5mm pitch connector. This port is not for operational use.

Pin

Service

1

DIAG_RTN

2

DIAG_IN_1

Table 3 Diagnostic Connector

1.4. PSU Shutdown Monitor Connector (J6)

J6 is Phoenix contact 2.5mm pitch connector. These two system inputs are made available to the
application on the Processor’s complex I/O equipment definition. The inputs expect volt-free contacts
to the RTN pin.

Pin

Service

1

24V_PSU1_SHUTDOWN

2

24V_PSU2_SHUTDOWN

3

24V_RTN

Table 4 PSU S/D Monitor Connection