Installing a d or e-frame enclosure kit – Rockwell Automation SA3100 Enclosure Kit User Manual

Page 3

Advertising
background image

Publication SA3100-5.11 - May 2000

SA3100 Enclosure Kit

3

Installing a D or E-Frame Enclosure Kit

1. Secure the extension plate with the supplied screws to 3 N-m (26 lb-in)

as shown in Figure 2.

2. Slide the side plates over the chassis tabs as shown in Figure 2.

3. Attach the top and bottom plates to the side plates by sliding the tabs into

the corresponding slots. Secure with the supplied screws to 2.8 N-m
(25 lb-in).

4. Install the door on the side plate hinge pins.

5. For EMC kits, fasten the supplied jumper wire between the chassis

ground stud and the lower corner of the door, as shown in Figure 2.
Torque the nut to 3 N-m (26 lb-in).

Figure 3
Installing a D or E-Frame Enclosure Kit

Door Grounding Jumper

Jumper must be installed
between the enclosure door
and chassis grounding stud.

For CE conformance, the EMI gasket
(pre-installed) and jumper supplied
with the kit must be in place.