Thermistor Replacement

A. Remove the thermistor lead (see photo below) from

the Power Interface Board. Remove the screw securing
the thermistor. Discard thermistor. Apply a thin film of
thermal grease (supplied) to the new thermistor and
replace in reverse order. Torque thermistor screw to
1.7 N-m (15 lbf.-in).

Power Interface Board Removal/Replacement

A. Remove upper sheet metal to access the board/

transducer(s).

B. Label and remove the wires/cables from the Power

Interface Board.

C. Remove the board.

D. If any of the Current Transducers are being replaced,

proceed to step

E.

If not, replace board and re-

assemble in reverse order.

Important: When replacing the Power Interface

Board, the six gate leads must also be
replaced with the leads supplied. Replace
the leads one-at-a-time to assure correct
orientation.

Tighten board screws to 1.7 N-m (15 lbf.-in.) and sheet
metal screws to 3.2 N-m (28 lbf.-in.).

Current Transducer Replacement

E. With the Power Interface Board still removed, locate

the transducer to be replaced.

F. Remove the screw securing the U, V or W lead that

extends through the transducer. Remove the lead from
the center of the transducer.

G. Remove the transducer by taking the 2 screws out.

Replace with new transducer and tighten screws to 1.7
N-m (15 lbf.-in.).

H. Replace the U, V or W lead and tighten screw to 4.5

N-m (40 lbf.-in.).

I. Replace the Power Interface Board.

Important: If a new board is being installed, the six

gate leads must also be replaced with the
new leads supplied. It is recommended
that the leads be replaced one-at-a-time to
assure correct orientation.

Tighten board screws to 1.7 N-m (15 lbf.-in.).

J. Re-assemble remainder of drive. Tighten sheet metal

screws to 3.2 N-m (28 lbf.-in.).

4

Transducer

Gate Leads

Power Interface Board

Thermistor Lead

www.rockwellautomation.com

Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846

Power, Control and Information Solutions Headquarters

Americas: Rockwell Automation, 6040 Ponders Court, Greenville, SC 29615-4617 USA, Tel: (1) 864.297.4800, Fax: (1) 864.281.2433
Europe/Middle East/Africa: Rockwell Automation, Herman-Heinrich-Gossen-Strasse 3, 50858 Köln, Germany, Tel: (49) 2234 379410, Fax: (49) 2234 3794164
Asia Pacific: Rockwell Automation, 55 Newton Road, #11-01/02 Revenue House, Singapore 307987, Tel: (65) 6356 9077, Fax: (65) 6356 9011

Motors, Drives and Power Transmission Solutions Headquarters

U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: [email protected], Online: www.ab.com/support/abdrives

U.S. Reliance Drives Technical Support - Tel: (1) 800.726.8112, Online: www.reliance.com

Publication RA-IN016A-EN-P – June, 2005

P/N 375847-P01

Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in USA.

Advertising