Rockwell Automation T8432 Trusted Dual Analogue Input Module User Manual

Sds-8432, Trusted, Industrial control system trusted

Advertising
background image

SDS-8432

Trusted

TM

Industrial Control System

Trusted

TM

Dual Analogue Input Module-T8432

Issue 5 Jan 2006

FRONT PANEL

DESCRIPTION


The Trusted

TM

Dual Analogue Input

module interfaces to 60 single-ended
field input devices. A wide input
voltage range and programmable
thresholds allow the module to be
used in current source and current
sink configurations. Comprehensive
diagnostic tests are performed on
each input channel, including tests for
stuck on and stuck off failures. Fault
tolerance is achieved through Dual
Redundancy within the same module
for each of the 60 input channels.

The module can apply a digital filter to
each

input

channel.

Individual

channels can be configured for high
noise immunity (50Hz or 60Hz
rejection), low noise immunity (fast
response), or pass-through operation
(no filtering).

Each

input

channel

has

four

configurable state thresholds which
may be assigned to SOE reporting. A
change of state triggers an SOE
entry. The on-board Sequence of
Events (SOE) reporting has a
resolution of 1ms.

Each dual section of the module,
referred to as a slice, conditions and
measures

each

channel

independently. Each slice is opto-
isolated up to 2500V dc. Each slice
sends its data to a safety layer
hardware voter that presents the
information from both slices to the
Trusted

TM

TMR Processor. When a

fault is detected on a slice of the
module,

the

Trusted

TM

TMR

Processor

will

flag

the

error,

indicating the need to replace the
module. The Trusted

TM

TMR

Processor will continue to use the
information provided by the remaining
slice until a replacement module is
available. Replacement modules can
be located in a standby slot next to
the module or in a designated
SmartSlot

with

a

temporary

connection to the same Trusted

TM

Termination Assembly.


Modules may be placed in any I/O

module slot in a Trusted

TM

Processor

Chassis or Expander chassis. Once
the I/O module configuration is set,
mechanical keying is available on all
I/O modules to prevent inserting a
module into an incorrect slot.

Configuration of the module is carried
out using the Trusted

TM

Toolset

running

on

an

Engineering

Workstation. Once configured and
loaded into the Trusted

TM

Controller,

replacement modules are on-line
educated by the TMR Processor.


FEATURES

60 input channels per module

Comprehensive diagnostics
and self-test

Line monitoring on a per
channel basis

2500V dc Opto-Isolation

On-board 1ms resolution
Sequence of Events reporting

Hot replaceable

Module fault and status
indicators

IEC 61508, SIL 3 safety
applications

Configurable per channel line
noise filter

T

8

4

3

2

T

ru

s

te

d

D

u

a

l

A

n

a

lo

g

u

e

In

p

u

t

Advertising