Block diagram, Electrical specification, Sds-8432 trusted – Rockwell Automation T8432 Trusted Dual Analogue Input Module User Manual
Page 2: Industrial control system trusted, Dual analogue input module-t8432
 
SDS-8432 
Trusted
TM
Industrial Control System
Trusted
TM
Dual Analogue Input Module-T8432
ICS Triplex 
 
Technical data sheets are intended for 
information and guidance. The Company 
has a policy of continual product 
development and improvement. 
Specifications are subject to change 
without notice. For latest information, visit 
our Website:- 
www.icstriplex.com
BLOCK DIAGRAM
ELECTRICAL SPECIFICATION
Number of Inputs
60 Channels
Field Common Isolation
Sustained Working
±250V dc
Maximum Withstanding
±2.5kV dc
Input Voltage
Measurement Range
±22mA
Maximum Withstanding
±25V dc
Channel Input termination 
Resistance 
2509
Power Consumption
15 to 18W
Sample Update Interval (no filter)
5ms
Self-Test Interval
2 minutes
Sequence of Events
Event Resolution
1ms
Time-stamp Accuracy
±0.5ms
Long Term Accuracy (at 25
0
C)
0.2% of span
Input Resolution
12 bit (1 part in 4096)
Fusing
None, external if required
Intrinsic Safety
External barrier
Circuit Type
Fault tolerant 1-00-2D
MECHANICAL 
SPECIFICATION 
 
Dimensions (HxWxD): 
241mm x 30mm x 300mm 
(9.5ins x 1.2ins x 11.8ins) 
 
Weight: 
1.13kg 
(2.5lbs) 
 
ENVIRONMENTAL
 
Operating Temperature: 
 
-5
°C to 60°C
(23
°F to 140°F)
 
Operating Humidity: 
5 to 95%, non-
condensing 
 
Vibration: 
10 to 57Hz 
±0.075mm
57 to 150Hz 1.0g 
 
Shock: 
15g, ½ sine wave, 11ms 
 
EMI (IEC 801): 
ESD 
Air discharge to 15kV 
Contact discharge to 8kV 
 
Radiated Fields 
10V/m, 27MHz to 
500MHz 
 
Transients and Bursts 
2kV, 2.5kHz for 
t=60 seconds