Maintenance, Safety considerations, Troubleshooting – Rockwell Automation T3491 ICS Regent Multiplexed I/O Modules User Manual
Page 17
 
Multiplexed I/O Module (T3491)
 
P D - 6 0 3 5 M a r - 0 6  
17
Maintenance
No periodic maintenance or calibration is required for the 
multiplexed I/O module. There are no user replaceable parts 
inside the module. 
Troubleshooting
Most problems with the Mux I/O equipment relates to 
improper configuration. For correct operation you should 
carefully check the protocol configuration (single vs. dual) and 
the MIU processor addresses. Verify the configuration 
information with the link settings for the MIU processors. 
Also you should carefully check the serial cable connections. 
The Mux I/O module labels the serial cable connections with 
‘A’ and ‘B’ designations although the MIU processors refer to 
the connections as ‘+’ and ‘-’. The serial cable connection 
diagram in Figure 4 properly illustrates the relationship 
between these signal references. 
Safety Considerations
The Multiplexed I/O module is TÜV certified as non-
interfering and may be used for non-safety critical inputs and 
outputs.
While the use of dual protocol configurations for 2oo2 voting 
provides greater security for the communications link, it is not 
sufficient to meet the requirements for Risk Class 5 safety 
critical inputs and outputs. In applications of Mux I/O 
equipment for maintenance override of safety critical inputs, 
redundant Mux I/O Modules and MIU equipment is 
recommended. 
For additional safety considerations, please refer to the Safety 
Considerations section of the Regent User’s Guide.