(T7404) AC Digital Input Module
 
P D - 7 0 1 3 M a r - 0 6  
5
Active and Fault Status Indicators
These green and red LEDs indicate the overall health of the 
module. During normal operation the green ACTIVE 
indicator flashes at the controller's scan rate. If a module 
fault is detected the red FAULT indicator turns on and the 
green indicator turns off. 
Field Status Indicators
Input status indicators are located on the logic-side (after the 
signal conditioning and isolation). The field status indicators 
are lit when current is flowing through the input. 
Application
Simplex Configuration
Digital input modules provide a suitable interface to non-
critical input signals. Although many of the circuits in the 
digital input modules are automatically tested and 
annunciated, some logic circuits and all of the field-side 
sensing circuits are simplex and non-tested. This simplex 
input configuration is illustrated in Figure 3. 
Figure 3. Simplex Digital Input Configuration.
Fault Tolerant Connection
For critical inputs, redundant input modules are used in a 
2oo3 or 1oo2 fault tolerant configuration. In these 
configurations the redundant input modules are connected to 
single or multiple sensors. If redundant sensors are installed