4.2. Communication Busses
4.2.1. Expander bus
Each TMR Expander Interface Module contains a Bus Interface, isolation components and
transceivers to the Expander Bus. The triplicated Expander Bus provides communication
interconnection between the TMR Processor Chassis and the Expander Chassis at a data transfer rate
of 1.5GMbps via UTP cables.
4.2.2. Inter-Module Bus
Each TMR Expander Interface Module FCR contains a Bus Interface to the Inter-Module Bus. The
triplicated Inter-Module Bus provides communication interconnection between modules in the TMR
Controller Chassis, at a data transfer rate of up to 12.5Mbps.
The Inter-Module Bus handles the following triplicated signals:
Data
- 8-bit, bi-directional bus.
Control
- Bus clocks, module enables and bus direction control.
System Watchdog - System Watchdog signal to the modules.
Power Fail
- System power fail warning to modules.
Slot
- Indicating the left or right Trusted
TM
TMR Expander Processor slot
position to the Trusted
TM
TMR Processor.
Chassis ID
- a 4-bit code indicating the chassis number or id.