Communication busses, Expander bus, Inter-module bus – Rockwell Automation T8311 Trusted Expander Interface User Manual

Page 21: Trusted, Module t8311

Advertising
background image

Trusted

TM

Module T8311

Issue 12 Mar 07

PD-T8311

21

4.2. Communication Busses

4.2.1. Expander bus

Each TMR Expander Interface Module contains a Bus Interface, isolation components and
transceivers to the Expander Bus. The triplicated Expander Bus provides communication
interconnection between the TMR Processor Chassis and the Expander Chassis at a data transfer rate
of 1.5GMbps via UTP cables.

4.2.2. Inter-Module Bus

Each TMR Expander Interface Module FCR contains a Bus Interface to the Inter-Module Bus. The
triplicated Inter-Module Bus provides communication interconnection between modules in the TMR
Controller Chassis, at a data transfer rate of up to 12.5Mbps.

The Inter-Module Bus handles the following triplicated signals:

Data

- 8-bit, bi-directional bus.

Control

- Bus clocks, module enables and bus direction control.

System Watchdog - System Watchdog signal to the modules.

Power Fail

- System power fail warning to modules.

Slot

- Indicating the left or right Trusted

TM

TMR Expander Processor slot

position to the Trusted

TM

TMR Processor.

Chassis ID

- a 4-bit code indicating the chassis number or id.

Advertising