Rockwell Automation 20D Fan/Transformer Replacement - Frame 5 User Manual

Fan/fan transformer replacement – frame 5, Installation instructions

Advertising
background image

Installation Instructions

Publication RA-IN009C

Fan/Fan Transformer Replacement – Frame 5

Fan Transformer Replacement

A. Remove the R, S & T power wires

from the terminal block. Remove the
screws from the cover plate. See

Figure 1

.

Figure 1

B. Lift the cover plate up and remove the transformer

connector from the circuit board. Position the board/
cover plate to allow access to the transformer.
See

Figure 2

.

Figure 2

C. Gain access to the two transformer screws by

repositioning the terminal block and/or rail. The rail can
be moved slightly by removing the end and middle
mounting screws. A slot in the chassis (below terminal
block) allows access to the back transformer screw.

D. Remove the two screws securing the transformer.

Remove transformer and note jumper placement.
Correctly position jumper on new transformer. Position
and secure new transformer to chassis with screws
previously removed. Re-assemble drive in reverse order.
All screws should be tightened to 3.2 N-m (28 lb.-in.).

1

L1

L2

L3

O

I

WIRE RANGE: 14-1/0 AWG (2.5-35 MM

2

)

TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM

2

)

TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM

2

)

TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

2

DC–

DC+

0V

0V

=

x 3