Fan/Fan Transformer Replacement – Frame 5

Publication RA-IN009C

Fan Replacement - IP00, NEMA/UL
Type 1 Drives

A. Remove the four screws securing the

plastic shield and HIM panel. Remove
the shield and lay the HIM Panel to one
side. Remove ground wire and MOV.

Figure 3

B. Remove screw securing fan cover. Remove fan connector.

Slide fan enclosure down & out (see

Figure 4

).

Figure 4

C. Remove fan assembly and replace fan.

D. Re-assemble in reverse order. Verify that notch on bottom

of assembly lines up with cut-out in chassis.

E. Verify Precharge Board alignment. Tighten all screws to

3.2 N-m (28 lb.-in.).

Fan Replacement - IP54, NEMA/UL
Type 12 Drives

A. Remove the four screws securing

the HIM panel. Position the HIM
Panel off to the side. Refer to

Figure 5

.

B. Locate the Fan Assembly and disconnect the cable.

Remove the 10 screws that secure the assembly. Pull the
Fan Assembly straight out and discard.

Figure 5

C. Install the new fan in reverse order.

D. Tighten all screws to 3.2 N-m (28 lb.-in.).

WIRE RANGE: 14-1/0 AWG (2.5-35 MM

2

)

TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM

2

)

TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM

2

)

TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

USE 75 C CU WIRE ONLY
WIRE RANGE: 4-3/0 AWG (18-70 MM2)
TORQUE: 133 IN-LB (15 N-M)
STRIP LENGTH: 1.02 IN (26 MM)

POWER & DC TERMINAL RATINGS

WIRE RANGE: 14-1/0 AWG (2.5-50 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)

BRAKE TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (18-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

OUTPUT

INPUT AC

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

DANGER

DANGER

RISK OF ELECTRIC
SHOCK AND DEATH

FIELD INSTALLED OPTIONS

6 MM HEX KEY

6 MM HEX KEY

SHLD

SHLD

x 10