Safety considerations, Specifications – Rockwell Automation T71xx Regent+Plus Processor Modules 110 VAC, 220/240VAC and 24VDC User Manual

Page 13

Advertising
background image

Processor Modules (T7110, 11, 12, 20, 21, and 22)


P D - 7 0 0 0 S e p - 0 4 (Issue 1)

1 3

Safety Considerations

Processor module catalog numbers T7110, T7112, T7120 and
T7122 are TÜV certified for Risk Class 5 safety critical

applications. Catalog numbers T7111 and T7121 (220 VAC

powered modules) have not been certified as they do not meet the
DIN VDE 0110 requirements for creepage and clearances.

Specifications

Voltage Range

T7110/T7120:
T7111/T7121:
T7112/T7122:

85 to 132 VAC
170 to 263 VAC
20 to 30 VDC

Frequency Range

T7110/T7120:
T7111/T7121:
T7112/T7122:


47 to 63 Hz
47 to 63 Hz

Maximum Load

100 VA

Fusing

2 A, 250 V, slo blo (3AG),

(located on controller chassis)

Use with Chassis

T7110/T7120:
T7111/T7121:
T7112/T7122:


T7100

T7101
T7102

Power Hold-Up Time

10 msec, minimum

Heat Dissipation

46 Watts, 156 BTUs/hour

Fault Contact Rating

(Class II Connection Only)

Load Current (max.):

Load

(min.):

Voltage

(max.):

Switching

Capacity

(max.):


1 amp
10 mV, 0.1 mA

30 VAC, 42.5 VDC

30 VA, 42.5 VAC (resistive)

Memory Size

128K:
512K:


T7110, T7111, T7112
T7120, T7121, T7122

Memory Type

Battery-backed CMOS RAM