Rockwell Automation T71xx Regent+Plus Processor Modules 110 VAC, 220/240VAC and 24VDC User Manual

Page 14

Advertising
background image

Processor Modules (T7110, 11, 12, 20, 21, and 22)


1 4
(Issue 1) I n d u s t r i a l

C o n t r o l

S e r v i c e s

Battery Type

Li/SO2

Battery Life

Under

Load:

Shelf

Life:


6 months

10 years

I/O Interface


Cable

Length:


I/O

Chassis:

Triple redundant I/O
Safetybus
150 cable feet (45 m),

maximum
16 chassis, maximum

Operating Temperature

0° to 60° C
(32° to 140° F)

Storage Temperature

-40° to 85° C
(-40° to 185° F)

Operating Humidity

0 to 95% relative humidity,
non-condensing

Vibration

10 to 55 Hz:


±0.15mm

Shock

Operating:


15 g, ½ sine wave, 11 msec

Electromagnetic
Interference

IEC 801 Part 2 - Electrostatic

Discharges

IEC 801 Part 3 - Radiated

Electromagnetic Fields

IEC 801 Part 4 - Transients

and Bursts

IEC 801 Part 5 - Surge

Immunity

ANSI/IEEE C37.90 - Surge

Withstand Capability



Level 3: Contact discharge of 6
kV
Level 3: 10 V/M, 27 MHz -

500 MHz
Level 4: 2 kV, 2.5 kHz for t =

60 sec
Level 3: 2 kV

2.5 kV damped 1 MHz sine

wave
4 kV bi-directional impulse, 10

nsec rise time, fast transient

Safety

Designed to meet UL 508 and
CSA 22.2, No. 142-M1981

Dimensions

Height:

Width:
Depth:

12.6" (320 mm)
1.27" (32 mm)
10.125" (257 mm)

Advertising