Triguard SC300E TDI16AIA 16-Channel D/I Termination Card 24Vdc

EXTERNAL CONNECTIONS

Fixed Terminal

Details

Field terminals 1 to 16 (+) and 1 to 16 (-)

Screw terminals to suit 2.5mm

2

wire

Chassis connector J1

Connector, 34-way,DIN41612,female

Field power supply inputs FS1 and FS2

Header, 2-way, Molex Minifit Jr

Alarm output PL1

Header, 2-way, Molex KK

Ground terminal TS1

Provision for M3 ring terminal

THEORY OF OPERATION

Figure 2-3 is a circuit diagram showing a typical digital input channel.

Power supplies for the termination cards are normally provided by a Power Distribution Panel
PDD24 which performs diode auctioneering of its dual redundant power supplies.

Power for the digital input circuits (normally from the PDD24) is fed to input FS1 or FS2. Where
the PDD24 is not used and dual supplies are required, these are connected to FS1 and FS2
respectively and auctioneered on the termination card by D17 and D18.

Each digital input channel is powered via an indicating fuse from a common +ve bus. The ‘fuse
failed’ output from each fuse is connected to a common alarm bus. If any fuse fails, local
indication is provided by the illumination of Fuse blown LED LD1. A signal to operate a remote
alarm is available at Alarm output PL1.

NOTE

The PDD24 has a Fuse blown alarm indicator with provision for multiple inputs. This facility can
be wired to provide fuse blown indication for an entire cabinet.

The -ve bus may be grounded via TS1 if required, preventing the power supplies from ‘floating’
when the chassis cable is disconnected.