Rockwell Automation TDI16AIA 16-Channel Digital Input Termination Card 24Vdc User Manual

Page 8

Advertising
background image

8

TAI16AIA October 2005 – Issue 3

Triguard SC300E

TRANSIENT SUPPRESSION

A transient suppressor is fitted across each digital input channel input to the SC300E chassis.
It provides a discharge path for transient energy pulses that may appear on the digital input line
following lightning strikes etc.

The suppressor is effectively a zener diode with a breakdown voltage just above that of the
normal supply voltage. In normal operation, therefore, the suppressor does not conduct (apart
from leakage current). In the presence of a transient pulse, zener breakdown occurs. The
voltage developed across the suppressor varies to some extent with the pulse current and is
known as the ‘clamping’ voltage.

The following characteristics are typical:

Table 2-1. Transient suppressor characteristics

Clamping

Voltage

Pulse

currents

Pulse

duration

Comments

+37V to +43V

*1mA

Continuous

*Maximum current continuous overload

+70V

**6gAmps

8 to 20

s

**Maximum peak pulse current

SUPPLEMENTARY INFORMATION

Table 2-2 lists the digital input channel wiring connections and associated fuses for connectors
J1 and J2.

Pin J1-1a is connected to the +ve bus (Figure 2-3 ). Pins J1-1c and J2-1c are interconnected.

J1/J2 pins other than J1-1a, J1-1c, J2-1c and those listed in Table 2-2 are not connected.

Advertising