Return Drive to Service

1. Remove power to the drive and wait for the Green LED on the Flash Module to go out.

Important: If power is reapplied to the drive too quickly, the drive can remain locked in the flash state. If this

occurs, remove power to the drive and wait 3 minutes before reapplying power.

2. Disconnect the DSI cable from port J2 on the drive control board.

3. Reconnect communication option if applicable.

4. Restore power to the drive.

• If the drive displays a F100 “Parameter Checksum” fault, cycle power to the drive. Repeat if the fault occurs

a second time.

5. Reset parameters to factory defaults. Access parameter P041 [Reset To Defalts] and set to “1”.

6. Access parameter d320 [Control SW Ver] and verify that the updated firmware version is installed.

7. Reprogram the drive for your application.