Rockwell Automation TDO16AIN 16-Channel Digital Output Termination Card Introducted Power 24Vdc User Manual

Page 2

Advertising
background image

2

TDO16AIN October 2005 – Issue 6

Triguard SC300E

SPECIFICATION

Model

TDO16AIN

Power supply inputs

Has four separate connectors (FS1, FS2, FS3
and FS4) for dc power supplies. The four
positive supplies feed individual sections of
the digital outputs via common buses. The
buses are linked together. For lightly loaded
applications (e.g. 6A) all the required power
can be supplied via one connector. For highly
loaded applications (e.g. 16A) use multiple
power connectors.

No. of digital input channels

16

Nominal field supply voltage

24Vdc

Maximum field supply voltage

33Vdc

Maximum field supply current

9A for each of the four input connectors (do
not exceed 16A total)

Fuse in each positive line to field

1A, fast acting, indicating

Chassis cable connector

34 way DIN41612

Field cable connector

Screw terminal to suit 2.5mm

2

wire (16 AWG)

Fuse blown indication

Local: Fuse blown LED (one per card)
Remote: Fuse blown alarm output (PL1) – can
be connected to Fuse blown LED on Power
Distribution Panel (PDD24).

Safety ground terminal TS1

M3 threaded bush provision for a ring terminal.
Allows the common 0V supply bus to be
grounded via a 10k ohm resistor. Prevents the
channels from floating if the card is
disconnected from the chassis.

Instrument 0V terminal TS2

M3 threaded bush provision for a ring terminal.
Allows the field 0V to be commoned for
transient suppression protection.

Overall size (mm)
Overall size (inches)

162L x 125W x 107H
6.4L x 4.9W x 4.2H

Weight

0.37kg

Advertising