MD60 / MD65 OIM Quick Reference

5

006 (Large Disp Param) - Selects the parameter

to display on the Large Format User Display
screen.
For example, setting to 1 selects parameter
D001 (Output Freq) on an MD60 drive.
Setting to 0 enables the Scaled Reference to
be displayed.

Default:
Minimum:
Maximum:
Type:

1
0
65535
Read/Write

007 (LCD Contrast) - Sets the LCD contrast level.

Default:
Minimum:
Maximum:
Type:

50%
0%
100%
Read/Write

008 (Reset Device) - Setting to 1 “Reset” resets

OIM.
Setting to 2 “Set Defaults” resets OIM
parameters to factory settings. The parameter
value returns to 0 “Ready” after the reset
function is complete.

Default:
Values:

Type:

0 = Ready
0 = Ready
1 = Reset
2 = Set Defaults
Read/Write

009 (Device Type) - Selects the OIM’s device type.

When set to 0 “Auto,” the OIM is automatically
configured as either an MDI Master or Slave
depending on the presence of other peripheral
devices.

Default:
Values:

Type:

0 = Auto
0 = Auto
1 = Slave
2 = Master
Read/Write

010 (M/S Status) - Displays the OIM’s active

device type.

Default:
Values:

Type:

N/A
1 = Slave
2 = Master
Read Only

011 (OIM Ref Preset)

Zero Start - OIM Reference is always 0.0 at
power on.

Host Output - OIM will assume the Host’s
output feedback (bumpless transfer) and
preset its Reference when the Reference is
configured to be received on the RS-485 port.
This can be verified by viewing Diagnostics/
Device Status/Remote Freq Ref = 1.

Last OIM Ref - OIM will store the OIM
Reference in EEPROM each time it is
changed. OIM Reference is restored at power
on.

Default:
Values:

Type:

0 = Zero Start
0 = Zero Start
1 = Host Output
2 = Last OIM Ref
Read/Write

012 (Ref Scaling) - Enables or disables scaling the

Reference to a user-defined value. Parameters
13-22 (Ref Units Char 1-8) are used when
parameter 012 (Ref Scaling) is “enabled.”

Default:
Values:

Type:

0 = Disabled
0 = Disabled
1 = Enabled
Read/Write

013 (Ref Max Value) - Selects the user-defined

value to display when the drive is running at 60
Hz.

Default:
Minimum:
Maximum:
Type:

600
100
65535
Read/Write

014 (Ref Dec Position) - Selects the number of

digits to the right of the decimal point for
Reference.

Default:
Minimum:
Maximum:
Type:

1
0
3
Read/Write

Table 3 – OIM Parameter List

No.

Name and Description

Details