I/o complex equipment definition t8310, Trusted, Module t8310 – Rockwell Automation T8310 Trusted Expander Processor User Manual

Page 19

Advertising
background image

Trusted

TM

Module T8310

Issue 12 Dec 06

PD-T8310

19

3.10. I/O Complex Equipment Definition T8310

Each module fitted in a Trusted

TM

system requires an entry in the I/O Connection table, specifying its

chassis and slot number. The I/O Complex Equipment Definition allows control of the module’s
functions, and provides information on its status. For information on editing the I/O Connection table,
refer to PD-8082B. The definition for this module is described below.

OEM PARAMETERS

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

2 – 15
13 and 14 (Expander Chassis)

The TICS chassis & slot number where the T8310 module
is placed. Expander processor modules cannot be placed
in a processor chassis.
By definition, the primary module is placed in the left-hand
slot (13) and the secondary in the right-hand slot (14).

CONFIGURATION

PHYSICAL MODULE:

RACK 1: [XPM_0]

16 ANALOGUE
inputs

Channel 1: Not used
Channel 2: 24V dc Feed 1
Channel 3: 24V dc Feed 2
Channel 4: Not used
Channel 5: Not used
Channel 6: Not used
Channel 7: Slice A Rx error count
Channel 8: Slice B Rx error count
Channel 9: Slice C Rx error count
Channels 10 to 16 – Not used.

RACK 2: (INFO)

11 INTEGER inputs

Channel 1:Chassis position of AM
Channel 2:Slot position of AM
Channel 3:Indication of global health of AM

1 – No slice errors and module is responding

0 – Some error has been found

Channel 4:Current state of AM
Channel 5:Chassis position of SM

0 – No partner exists

Channel 6:Slot position of SM

0 – No partner exists

Channel 7:Indication of global health of SM

1 – No slice errors and module is responding

0 – Some error has been found

Channel 8:Current state of SM
Channel 9:Slice information of SM. See Note
Channel 10

Is AM the Primary Module

1 – Yes 0 – Not

Channel 11:Not used

Advertising