Application, Setting the real-time clock – Rockwell Automation T3151 ICS Regent Real time Clock Communications Modules User Manual
Page 7
 
Real-Time Clock Communications Modules (T3151)
 
P D - 6 0 0 3 M a r - 0 6  
7
Application
Setting the Real-Time Clock
The real-time clock is set by loading the associated system 
variable registers with the desired time and date values and 
subsequently turning on the RTCSET system variable control 
relay. The W
INTERPRET
application can be used to perform
this function using the Set Real-Time Clock command from 
the Project Editor’s Controller menu. This command opens 
the dialog shown in Figure 3. In the Set Real-Time Clock 
dialog enter the desired values for Month, Day, Year, Hour, 
Minute and Second (milliseconds are automatically set to zero 
when the clock is set). Choose OK to send the values to the 
Regent. 
Figure 3. W
INTERPRET
’s Set Real-Time Clock Dialog.
By reading and writing to the real-time clock system registers, 
other communications equipment can read and set the real-
time clock. The associated system variables are listed in 
Table 1. The “Set” values are sent to the real-time-clock 
communications modules when the system variable control 
relay RTCSET is turned on.