Communication port connections – Rockwell Automation T3151 ICS Regent Real time Clock Communications Modules User Manual
Page 8
Real-Time Clock Communications Modules (T3151)
 
8  
Industrial Control Services
Table 1. Real-Time Clock System Registers.
Unit
Read Clock 
Tag Name 
Set Clock 
Tag Name 
Year
RTCYEAR
SETYEAR
Month
RTCMNTH
SETMNTH
Day of Month
RTCDOM
SETDOM
Day of Week
RTCDOW
SETDOW
Hour
RTCHOUR
SETHOUR
Minute
RTCMIN
SETMIN
Second
RTCSEC
SETSEC
Millisecond
RTCMS
(always set to 0)
Communication Port Connections
Each communications port has a DB-25, female connector on 
the front of the module. The RS232 signals are internally 
connected to the DB-25 connector pins listed in Table 2. 
Table 2. Communications Port Pin-out.
Signal
Pin
TXD
2
RXD
3
GND
7
Typically these ports are used to connect to a communications 
device located within 150 feet of the system. For longer 
distances, external modems or signal converters may be used. 
Since the module only provides RS232 interface connections, 
external signal converters (RS232 to RS422/485) are required 
if the module is to be connected in multidrop configurations. 
These configurations may include Guarded Peer-Link to other 
Regents or multidrop networks to a central PC, Man-Machine 
Interface or other communications devices (that support the 
Regent R2 or Modbus RTU protocols).