Figure 10. Limits on Number of Variable Entries and Frames.

Size of the Process Historian Function Block

The Process Historian function block is slightly larger than
the size of the historical buffer calculated above. The
equation below is used to calculate the overall size of the
function block.

FB Size = 36 + (4 * QtyTOTAL) + Buffer Size

Where:

FB Size

=

Size of Process Historian

function block

QtyTOTAL

=

Number of process variables
defined in function block regardless
of data type

Buffer Size

=

Size of Historical Buffer calculated
above