Rockwell Automation T3512 ICS Regent Power Supply Modules User Manual

Ics regent, I/o power supply modules, Module operation

Advertising
background image

ICS Regent

®

PD-6008

Industrial Control Services

1

I/O Power Supply Modules

110 VAC, 220/240 VAC and 24 VDC

(T3510, T3511 and T3512)

Issue 1, March, 06

I/O power supply modules convert main line voltages of either
110 VAC, 220/240 VAC or 24 VDC to +15 VDC power that is
used to drive the I/O assembly (I/O chassis, I/O modules, and
I/O transceivers).

Three I/O power supply modules installed in an I/O power
supply chassis make up a triple redundant power supply unit.

Features

·

Three modules provide triplicated power to as many as four

I/O assemblies.

·

Hot replaceable.

·

Front panel indicator on each module shows DC output

status.

·

TÜV certified for safety, Risk Class 5 (see Safety

Considerations).

Failed I/O power supply modules can be hot replaced without
interrupting system operation.

Module Operation

Triplicated Power Distribution

Each of the triple redundant I/O power supply modules within
the I/O power supply assembly provides power for one leg of
the three redundant legs of the I/O Safetybus transceivers,
and provides power to all the I/O modules within its associated
I/O chassis. Each I/O module contains a diode OR power-

Advertising