I/O Power Supply Modules (T3510, 11, and 12)


8

Industrial Control Services

Shock

Operating:


15 g, ½ sine wave, 11 msec

Electromagnetic
Interference

IEC 801 Part 2 - Electrostatic

Discharges

IEC 801 Part 3 - Radiated

Electromagnetic Fields

IEC 801 Part 4 - Transients

and Bursts

IEC 801 Part 5 - Surge

Immunity

ANSI/IEEE C37.90 - Surge

Withstand Capability


Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz -
500 MHz
Level 4: 2 kV, 2.5 kHz for t =
60 sec
Level 3: 2 kV

2.5 kV damped 1 MHz sine
wave
4 kV bi-directional impulse,
10 nsec rise time, fast
transient

Safety

Certified to DIN V VDE
0801 for Risk Class 5. Also
designed to meet UL 508 and
CSA 22.2, No. 142-M1981

Dimensions

Height:

Width:

Depth:


13.0" (330 mm)
4.12" (105 mm)
10.25" (260 mm)

Weight

7.5 lbs (3.4 kg)