Model LF127W and

LFF127W

High Capacity Water Pressure

Reducing Valves

Size: 3" - 4"

Model LF127W and LFF127W High Capacity Water Pressure

Reducing Valves are designed to reduce incoming water pres-

sure to a sensible level to protect plumbing system components

and reduce water consumption. The LF127W and LFF127W are

remote control type regulators ideal for commercial and industrial

applications where a regulator must reach full capacity with a

minor drop in reduced pressure. These models are also suit-

able for applications where close pressure regulation is required

through extensive volume demand. These models are suitable

for water supply pressures up to 175psi (12.1 bar) and may be

adjusted from 25 – 100psi (172 – 690 kPa). All parts are quickly

and easily serviceable.
The LF127W and LFF127W feature Lead Free* construction to

comply with Lead Free* installation requirements.

Features

•  Lead Free* body construction
•  Replaceable stainless steel seat
•  Outstanding maintenance features
•  Close control of reduced pressure
•  High temperature-resisting diaphragm
•  Interchangeable diaphragm chamber

Specifications

A Water Pressure Reducing Valve shall be installed on the water

service pipe near its entrance to the building where supply

main pressure exceeds 60psi (413 kPa) to reduce it to 60psi

(413 kPa) or lower. The water pressure reducing valve shall be

constructed using Lead Free* materials. Lead Free* regulators

shall comply with state codes and standards, where applicable,

requiring reduced lead content. The valve shall be equipped with

a

3

8

" tapping to receive equalizer piping and a

3

4

" tapping to

receive auxiliary regulator piping for low flow requirements. Valve

shall be a Watts Model LF127W or LFF127W.

* The wetted surface of this product contacted by consumable

water contains less than 0.25% of lead by weight.

Materials

For Commercial and Industrial Applications

ES-LF127W

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer ––––––––––––––––––––––––––––––––––––––––––––– 

Contractor’s P.O. No.   ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

3" (80mm) LF127W

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

LEAD FREE

*

6", 8" or 10"

(150, 178, or 200mm)

depending upon reduced

pressure range.

Diaphragm chamber

is easily changed by

the removal of

two cap screws.

High

temperature-resisting

diaphragm.

Requirements of various

pressure conditions can

be quickly met by

interchanging the various

sizes of diaphragm cham-

bers - 6", 8", 10"

(150, 178, 200mm)

as well as by interchanging

spring.

Stainless steel stem.

Replaceable

stainless

steel seat.

Tapping provided in

low pressure side of

body for 4" valve to

permit convenient,

economical attachment

of equalizer line.

Advertising