Watts LF25AUB-Z3 User Manual

Series lf25aub-z3, Lead free, Water pressure reducing valves

Advertising
background image

For Residential and Commercial Applications

ES-LF25AUB

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

LF25AUB-Z3

EPDM

diaphragm

Integral

stainless

steel strainer

Union inlet

connection

Replaceable

seat module

Bypass valve

assembly for 1

1

4

" – 2"

(32 – 50mm) sizes

Bypass for

1

2

" – 1"

(15 – 25mm)

sizes

Series LF25AUB-Z3

Water Pressure Reducing Valves**

Sizes:

1

2

" – 2" (15 – 50mm)

Series LF25AUB-Z3 Water Pressure Reducing Valves are designed to reduce

incoming water pressure to a sensible level to protect plumbing system

components and reduce water consumption. This series is suitable for water

supply pressures up to 300psi (20.7 bar) and may be adjusted from 25 – 75psi

(172 – 517 kPa). The LF25AUB-Z3 features Lead Free* construction to comply

with Lead Free* installation requirements. The standard setting is 50psi (345

kPa). All parts are quickly and easily serviceable without removing the valve

from the line. The standard bypass feature permits the flow of water back

through the valve into the main when pressures, due to thermal expansion on

the outlet side of the valve, exceed the pressure in the main supply.

Features

•   Standard construction includes Z3 sealed spring cage and stainless steel 

corrosion resistant adjusting & cage screws for accessible outdoor

or pit installations

•  Union inlet connection

•  Integral stainless steel strainer

•  Replaceable seat module

•  Lead Free* cast copper silicon alloy construction

•  Serviceable in line

•  Bypass feature controls thermal expansion pressure***

•  High temperature resistant reinforced diaphragm for hot water

Models

LF25AUB-Z3

NPT threaded female union inlet x NPT female outlet

LF25AUB-S-Z3

Solder union inlet x NPT female outlet

LF25AUB-DU-Z3

Double Union – NPT threaded union female inlet and outlet

LF25AUB-S-DU-Z3

Double Union – Solder union inlet and outlet

LF25AUB-DU-THDxPEX-Z3 Double Union – NPT threaded female inlet

and PEX union outlet

LF25AUB-DU-LF-Z3

Double union body less fittings (

3

/

4

", 1", 1

1

/

4

")

LF25AUB-QC-Z3

Single Union – Quick-Connect union inlet (

1

/

2

",

3

/

4

", 1")

LF25AUB-DU-QC-Z3

Double Union – Quick-Connect inlet and outlet

(

1

/

2

",

3

/

4

", 1")

Specifications

A Water Pressure Reducing Valve with integral strainer shall be installed in the water

service pipe near its entrance to the building where supply main pressure exceeds

60psi (413 kPa) to reduce it to 50psi (345 kPa) or lower. The water pressure reduc-

ing valve shall be constructed using Lead Free* materials. Lead Free* regulators

shall comply with state codes and standards, where applicable, requiring reduced

lead content. The valve shall feature a Lead Free* cast copper silicon alloy suitable

for water supply pressures up to 300psi (20.7 bar). Provision shall be made to permit

the bypass flow of water back through the valve into the main when pressures, due

to thermal expansion on the outlet side of the valve, exceed the pressure in the main

supply. Water Pressure Reducing Valve with built-in bypass check valves will be

acceptable. Approved valve shall be listed to ASSE 1003 and IAPMO and certified to 

CSA B356. Valve shall be a Watts Series LF25AUB-Z3.

LEAD FREE

*

* The wetted surface of this product contacted by consumable

water contains less than 0.25% of lead by weight.

** A water saving test program concluded that reducing the supply

pressure from 80-50psi (551-345 kPa) resulted in a water savings
of 30%.

*** The bypass feature will not prevent the pressure relief valve from

opening on the hot water supply system with pressure above
150psi (10.3 bar).

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.