Watts LFN223BS User Manual

Lead free, Super capacity water pressure reducing valves

Advertising
background image

Series LFN223B,

LFN223BS

Super Capacity Water Pressure

Reducing Valves**

Sizes: 2

1

2

" – 3"

Series LFN223B and LFN223BS Super Capacity Water Pressure Reducing

Valves are designed to reduce incoming water pressure to a sensible

level to protect plumbing system components and reduce water con-

sumption. The LFN223B/LFN223BS features Lead Free* construction to

comply with Lead Free* installation requirements. This series is suitable

for water supply pressures up to 300psi (20.7 bar) and may be adjusted

from 25 – 75psi (172 – 517 kPa). The standard setting is 50psi (345

kPa). Series LFN223B features an enlarged diaphragm, spring cage and

seat orifice for super capacity performance. Series LFN223BS has the

same options as the LFN223B, except it is furnished with a Lead Free*

strainer. All parts are quickly and easily serviceable without removing

the valve from the line. The standard bypass feature permits the flow

of water back through the valve into the main when pressures, due to

thermal expansion on the outlet side of the valve, exceed the pressure in

the main supply.

Features

•   Enlarged diaphragm, spring cage and seat orifice for super 

capacity performance

•   Lead Free* cast copper silicon alloy body construction
•   Serviceable in line
•   Series LFN223BS furnished with separate Lead Free* strainer
•   Standard bypass feature controls thermal expansion pressure***
•   Sealed spring cage on all models for accessible outdoor or pit installations

Specifications

A Lead Free* Water Pressure Reducing Valve shall be installed on the

water service pipe near its entrance to the building where supply main

pressure exceeds 60psi (413 kPa) to reduce it to 50psi (345 kPa) or

lower. The water pressure reducing valve shall be constructed using

Lead Free* materials. Lead Free* regulators shall comply with state

codes and standards, where applicable, requiring reduced lead content.

Provision shall be made to permit the bypass flow of water back through

the valve into the main when pressures, due to thermal expansion on

the outlet side of the valve, exceed the pressure in the main supply.

Pressure reducing valves with built-in bypass check valves and strainer

will be acceptable. Approved valves shall comply with ASSE 1003. Valve 

shall be a Watts Series LFN223B or LFN223BS (with strainer).

For Commercial, Institutional and Industrial Applications

ES-LFN223B

Available with or without

separate strainer

Disc holder removable for replacement of

disc without dismantling the valve —

no special tools required.

Sensitive spring and large

diaphragm area for accurate

pressure control

Lead Free*

brass body

construction

Renewable

stainless steel

alloy seat

Large stainless steel

perforated strainer screen

Sealed spring cage

Series LFN223B

LEAD FREE

*

* The wetted surface of this product contacted by consumable

water contains less than 0.25% of lead by weight.

** A water saving test program concluded that reducing the supply

pressure from 80-50psi (551-345 kPa) resulted in a water savings
of 30%.

*** The bypass feature will not prevent the pressure relief valve from

opening on the hot water supply system with pressure above
150psi (10.3 bar).

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Bypass

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

NOTICE

Inquire with governing authorities for local installation requirements