Watts LFN250 User Manual

Series lfn250, Lead free, Iron body water pressure reducing valves

Advertising
background image

size (dn)

dimensions

weight

A B C

in. mm

in. mm

in. mm

in. mm

lbs. kgs.

1

2

15 4 102 1

5

8

41 3

7

8

98 2.5 1.1

3

4

20 4

5

16

110 1

3

8

35

5 127 3.5 1.6

For Residential Applications

ES-LFN250

Job Name –––––––––––––––––––––––––––––––––––––––––––– Contractor

––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––– Approval

––––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative

–––––––––––––––––––––––––––––––––––––––––

Series LFN250

Iron Body Water Pressure

Reducing Valves**

Sizes:

1

2

" –

3

4

" (15 – 20mm)

Series LFN250 Iron Body Water Pressure Reducing Valves are

designed to reduce incoming water pressure to a sensible level to

protect plumbing system components and reduce water consump-

tion. This series is suitable for water supply pressures up

to 250psi (17.2 bar) and may be adjusted from 25 – 75psi

(172 – 517 kPa). The standard setting is 50psi (345 kPa). All parts

are quickly and easily serviceable without removing the valve from

the line. The optional bypass feature permits the flow of water back

through the valve into the main when pressures, due to thermal

expansion on the outlet side of the valve, exceed the pressure in the

main supply. The LFN250 features Lead Free* construction to comply

with Lead Free* installation requirements.

Features

• Integral strainer
• Unitized construction for ease of maintenance
• High temperature resisting diaphragm for hot or cold water
• All working parts easily and quickly serviceable without

removing the valve from the line

• Optional bypass feature controls thermal expansion pressure***

Models

LFN250 – NPT threaded female inlet x NPT female outlet
LFN250B – NPT threaded female inlet x NPT female outlet

with thermal expansion bypass feature

Note: Cast iron body regulators are not intended for buried or pit

services.

Specifications

A Water Pressure Reducing Valve and strainer shall be installed on

the water service pipe near its entrance to the building where supply

main pressure exceeds 60psi (413 kPa) to reduce it to 50psi (345 kPa)

or lower. Provision shall be made to permit the bypass flow of water

back through the valve into the main when pressures, due to thermal

expansion on the outlet side of the valve, exceed the pressure in the

main supply. Pressure reducing valves with built-in bypass check

valves and integral strainer will be acceptable. Valve shall be a Watts

Series LFN250.

Materials

Body: Iron
Seat: Stainless steel
Integral Strainer: Stainless steel
Stem: Lead Free* brass
Disc: Lead Free* brass

Pressure — Temperature

Temperature Range: 33°F – 160°F (0.5°C – 71°C)

Maximum Working Pressure: 250psi (17.2 bar)

Adjustable Reduced Pressure Range: 25 – 75psi (172 – 517 kPa)

Standard Reduced Pressure Setting: 50psi (345 kPa)

* The wetted surface of this product contacted by consumable

water contains less than 0.25% of lead by weight.

** A water saving test program concluded that reducing the supply pres-

sure from 80 – 50psi (551 – 345 kPa) resulted in a water savings of 30%.

*** The bypass feature will not prevent the pressure relief valve from opening

on the hot water supply system with pressure above 150psi (10.3 bar).

LFN250

Dimensions — Weights

A

B

C

ES-LFN250 1315

© 2013 Watts

USA: Tel. (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts
reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications
on Watts products previously or subsequently sold.

A Watts Water Technologies Company