Watts LFM1115 User Manual

Lead free, Pressure reducing control valve, Mustang series

Advertising
background image

○ X – Isolation Cocks

○ FC – Flo-Clean Strainer

○ Y – Y-Strainer (Replaces Flo-Clean)

○ ACS – Adjustable Closing Speed

(Replaces Fixed Orifice)

○ AOS – Adjustable Opening Speed

○ P – Position Indicator

○ L

– Limit Switch

Options & Accessories

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

LEAD FREE

*

Mustang Series

ES-ACV-SB-LFM115_LFM1115

Standard Components

(3)

(3)

(3)

(2)

(2)

(1)

(1)

Standard 3" & Smaller

Standard 4" & Larger

Optional All Sizes

(3)

(2)

(1)

Schematic

• Throttles to reduce high upstream pressure to

constant lower downstream pressure

1

X

X

X

Y/FC

P/L

3

2

CLOSES VALVE

OPENS VALVE

FLOW

(AOS)

LFM115 (Globe) LFM1115 (Angle)

Pressure Reducing Control Valve

Operations

1 – Main Valve (Single Chamber)

2 – Pressure Reducing Control

3 – Fixed Orifice

• Reducing setpoint is adjustable

The Watts ACV Pressure Reducing Control Valve is designed to automatically reduce a fluctuating higher

upstream pressure to a constant lower downstream pressure regardless of varying flow rates. It is con-

trolled by a normally open, pressure reducing pilot designed to: 1) Open (allowing fluid out of the main

valve cover chamber) when downstream pressure is below the adjustable setpoint, and 2) Close (allowing

fluid to fill the main valve cover chamber) when downstream pressure is above the adjustable setpoint. A

decrease in downstream pressure causes the valve to modulate toward an open position, raising down-

stream pressure. An increase in downstream pressure causes the valve to modulate toward a closed

position, lowering downstream pressure.

*The wetted surface of this product contacted by consumable