Installation, Maintenance, & Repair

Series 757, 757DCDA & LF757DCDA

Double Check Valve Assemblies

Double Check Detector Assemblies

Sizes: 2

1

2

" – 10" (65 – 250mm)**

NOTICE

For Australia and New Zealand, line strainers should be installed

between the upstream shutoff valve and the inlet of the backflow pre-

venter.

Testing

For field testing procedure, refer to Watts installation sheets

IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on

www.watts.com.
For other repair kits and service parts, refer to our Backflow

Prevention Products Repair Kits & Service Parts price list

PL-RP-BPD found on

www.watts.com.

For technical assistance, contact your local Watts representative.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can

result in death, serious personal injury, property damage, or

damage to the equipment.
Keep this Manual for future reference.

You are required to consult the local building and plumbing
codes prior to installation. If the information in this manual
is not consistent with local building or plumbing codes,
the local codes should be followed. Inquire with governing
authorities for additional local requirements.

WARNING

!

Need for Periodic Inspection/Maintenance: This product must

be tested periodically in compliance with local codes, but at least

once per year or more as service conditions warrant. If installed on

a fire suppression system, all mechanical checks, such as alarms

and backflow preventers, should be flow tested and inspected in

accordance with NFPA 13 and/or NFPA 25. All products must be

retested once maintenance has been performed. Corrosive water

conditions, and/or unauthorized adjustments or repair could render

the product ineffective for the service intended. Regular checking

and cleaning of the product’s internal components helps assure

maximum life and proper product function.

WARNING

!

Most field problems occur because dirt and debris present in the

system at the time of installation become trapped in the #1 check.

The system should be flushed before the backflow valve is

installed. If the system is not flushed until after the backflow valve

is installed, remove both check modules from the valve and open

the inlet shutoff to allow water to flow for a sufficient time to flush

debris from the water line. If debris in the water system continues

to cause fouling, a strainer can be installed upstream of the back-

flow assembly.

Watts Series 757 and 757DCDA/LF757DCDA may be installed in

either horizontal or vertical position as long as the backflow assem-

bly is installed in accordance with the direction of the flow arrow

on the assembly and the local water authority approves the instal-

lation. The assembly should be installed with adequate clearance

around the valve to allow for inspection, testing and servicing. 12"

should be the minimum clearance between the lower portion of the

assembly and the floor or grade.

NOTICE

Assembly body should not be painted.

Installation Guidelines

** Metric Dimensions are nominal pipe diameter. This product is

produced with ASME/ANSI flanged end connections.