Watts S1513-6 User Manual

Stainless series, S6500, Standard materials

Advertising
background image

Stainless Series

R

01/05

Standard Materials

Body & Cover: Ductile Iron ASTM A536

Coating:

NSF Listed Fusion
Bonded Epoxy Lined

Standard Materials

Body & Cover: Ductile Iron ASTM A536

Coating:

NSF Listed Fusion
Bonded Epoxy Lined
and Coated

Trim:

316 Stainless Steel


Elastomers:

Buna-N (standard)

EPDM (optional)
Viton (optional)

S6500 LINK

C

H

A

B

D

E

F G

I

H

Globe

Angle

S6500

(Globe)

S61500 (Angle)

Dimensions

A

B

C

D

E

F

G

H

I

VALVE

SIZE

GLOBE

150#

GLOBE

300#

COVER TO

CENTER

ANGLE

150#

ANGLE

300#

ANGLE

150#

ANGLE

300#

PORT

SIZE

PORT

SIZE

SHIPPING

WEIGHTS*

6

17-3/4

18-5/8

11-5/8

8-7/8

9-3/8

6-3/4

7-1/4

3/4

3/4

77

8

21-3/8

22-3/8

15

10-11/16

11-3/16

7-1/4

7-3/4

1

3/4

168

10

26

27-3/8

17-7/8

1

1

225

12

30

31-1/2

21

1

1-1/4

376

16

35

36-5/8

25-3/4

1

1-1/4

450

18

48

49-5/8

31

1

1-1/2

850

20

48

49-5/8

31

1

1-1/2

860

24

48

49-3/4

31

1

1-1/2

870

*Estimated in lbs.

Description

The Watts ACV Models S6500 and S61500 are reduced port, dual chamber basic valves that incorporate a one-piece disc and
diaphragm assembly. This assembly is the only moving part within the valve, allowing it to open or close as commanded by the pilot
control system.

When pressure is applied to the upper diaphragm chamber and released from the lower diaphragm chamber, the valve travels to a
closed position. When pressure is applied to the lower diaphragm chamber and released from the upper diaphragm chamber the
valve travels to a full open position. When pressure is balanced between the upper and lower diaphragm chambers, the valve will
hold an intermediate position until commanded to modulate open or closed by the pilot control system.

The Stainless Steel design offers superior corrosion resistance, as well as a lightweight alternative to conventional heavy iron
valves. Stainless Steel construction provides extended, diaphragm life and reduces the frequency and labor costs associated with
traditional maintenance repairs.

Model S6500: Globe Pattern Dual Chamber Basic Valve
Model S61500: Angle Pattern Dual Chamber Basic Valve

Operating Pressure

150 Flanged = 250 psi / 300 Flanged = 400 psi

Operating Temperature

Buna-N: 160°F Maximum
EPDM: 300°F Maximum
Viton: 250°F Maximum

8550 Hansen Road

Houston, Texas 77075

(Ph) 713.943.0688

(Fx) 713.944.9445

www.wattsacv.com

Advertising