Watts 957Z User Manual

Installation instructions

Advertising
background image

957 OSY

RP/IS-957/957RPDA

Installation, Maintenance, & Repair
Series 957, 957RPDA, LF957RPDA

Reduced Pressure Zone Assemblies

Reduced Pressure Detector Assemblies

Sizes: 2

1

2

" – 10" (65 – 250mm)

NOTICE

For Australia and New Zealand: Pipeline strainers should be

installed between the upstream shutoff valve and the inlet of the

backflow preventer.

It's important that this device be tested periodically in compli-

ance with local codes, but at least once per year or more as

service conditions warrant. If installed on a fire sprinkler system,

all mechanical checks, such as alarm checks and backflow

preventers, should be flow tested and inspected internally in ac-

cordance with NFPA 13 and NFPA 25.

Testing

For field testing procedure, refer to Watts installation sheets

IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on

www.watts.com.
For other repair kits and service parts, refer to our Backflow Pre-

vention Products Repair Kits & Service Parts price list

PL-RP-BPD found on

www.watts.com.

For technical assistance, contact your local Watts representative.

Local building or plumbing codes may require modifi cations to

the information provided. You are required to consult the local

building and plumbing codes prior to installation. If this informa-

tion is not consistent with local building or plumbing codes, the

local codes should be followed.
Need for Periodic Inspection/Maintenance: This product

must be tested periodically in compliance with local codes, but

at least once per year or more as service conditions warrant.

Corrosive water conditions, and/or unauthorized adjustments

or repair could render the product ineffective for the service in-

tended. Regular checking and cleaning of the product’s internal

components helps assure maximum life and proper product

function.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information

can result in death, serious personal injury, property

damage, or damage to the equipment.
Keep this Manual for future reference.

Guidelines

1. Most field problems occur because dirt and debris are pres-

ent in the system at the time of installation and becomes

trapped in the #1 check. The system should be flushed

before the backflow valve is installed. If the system is not

flushed until after the backflow valve is installed, remove both

check modules from the valve and open the inlet shutoff to

allow water to flow for a sufficient time to flush debris from

the water line. If debris in the water system continues to

cause fouling, a strainer can be installed upstream of the

backflow assembly.

2. Watts Series 957, 957RPDA and LF957RPDA may be in-

stalled in either horizontal, “N” pattern, or “Z” pattern position

as long as the backflow assembly is installed in accordance

with the direction of the flow arrow on the assembly and the

local water authority approves the installation.

3. The assembly should be installed with adequate clearance

around the valve to allow for inspection, testing and servic-

ing. 12" (305mm) should be the minimum clearance between

the lower portion of the assembly and the floor or grade. The

valve should be protected from freezing.

4. Installing a backflow preventer in a pit or vault is not recom-

mended.

5. Normal discharge and nuisance spitting are accommodated

by the use of a Watts air gap fitting and a fabricated indirect

waste line. Floor drains of the same size must be provided in

case of excessive discharge.

6. The 957, 957RPDA and LF957RPDA backflow preventer

should be tested by a certified tester at the time of installa-

tion.

NOTICE

Assembly body should not be painted.

Installation Instructions

Series 957, 957RPDA, LF957RPDA

Advertising
This manual is related to the following products: