Watts PWR4021 User Manual

Pure water, Series pwr4021, Commercial reverse osmosis systems

Advertising
background image

For Commercial Applications

ES-WQ-PWR4021

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Series PWR4021

Series PWR4021

Commercial Reverse Osmosis

Systems

Flow Rates: Up to 10,800 gpd (40,878 lpd)

Watts Pure Water Series PWR4021 reverse osmosis (RO)

systems are commercial grade high-pressure RO units for

the reduction of total dissolved solids from water. They are

designed to supply reverse osmosis quality water with pro-

duction rates ranging from 3,600 to 10,800 gallons per day

(40,878 lpd).These units are designed for floor mount instal-

lations. Reverse osmosis is a process where high-pressure

feed water is fed into a semi-permeable membrane. In the

membrane, pure water is allowed to pass through the mem-

brane material and exit as purified permeate water. Dissolved

mineral salts are not allowed to pass through the membrane

and become a concentrated reject stream that is sent to a

drain. These RO systems use high-pressure/high-rejection

membranes to achieve a minimum average NaCl ionic rejection

of 95 percent.
Watts Pure Water Series PWR4021 RO systems are a well

designed, rugged line of purifiers. This series comes with a pre-

selected assortment of features, including our digital controller,

for monitoring and operation. Stainless steel membrane hous-

ings, inlet and outlet pre-filter pressure gauges, low-pressure

switch with delayed auto restart, inputs for tank level and

pretreatment interlock, conductivity meter, high-conductivity

alarm output, adjustable reject recycle, permeate and reject

water flow meters, reject recycle flow meter, permeate water

check valve, inlet solenoid valve, membrane feed and reject

water pressure gauges, auto flush, and adjustable reject valve

are all standard features. These systems are designed to

feed an atmospheric storage tank for collection of the reverse

osmosis water. Reverse osmosis water has a wide variety of

applications including municipal water treatment, steam boiler

and steam sterilizer make up, laboratory use, spot free rinsing,

ice and beverage water, water for cooking, food processing,

metal plating and finishing, as well as water for humidification.

Reverse osmosis is also the pretreatment of choice for ion

exchange type de-ionization (DI) systems. Using RO water as

make up to a DI system reduces the exhaustion rate of the DI

resin by up to 95 percent saving time, money, and chemicals

associated with DI resin regeneration.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Features

• Membrane Auto Flush
• Powder coated carbon steel support frame
• 316L stainless steel 300psi high-pressure membrane

housings

• Pressure gauges for pre-filter inlet/outlet, membrane feed,

and reject water pressure

• Low feed water pressure safety switch
• Digital microprocessor based controller with delayed auto

restart after low-pressure shut down

• Permeate water conductivity meter with high-conductivity

alarm output

• Tank level and pretreatment interlock inputs
• High-pressure/high-rejection membranes with 95% minimum

average salt rejection

• Permeate, reject recycle, and reject water flow meters
• Adjustable reject and reject recycle valves
• Permeate check valve
• Automatic inlet solenoid valve
• 20" high flow pre-filter

Standards

• Pre-filter Housing NSF/ANSI Certified 42

PURE WATER

Note:

Do not use with water that is microbiologically unsafe or

of unknown quality without adequate disinfection before or after

the system.