8

Controls

(see Figure 2)

NOTE: Refer to Section III, Operation for detailed instructions

on operating the controls .
Start / Stop Button: This button turns the system on and off.
Select Button: This button is used to select a function or parameter

so that it can be reviewed or changed.
Up Arrow. This button increases the value of, or advances to the

next option of, the function selected.
Down Arrow. This button decreases the value of, or advances to the

next option of, the function selected.
Accept Button: Pressing this button causes the controller to store

current values or options in memory.
Alarm Reset Button: This button is used to reset the system after a

shut down due to; low-pressure or overload.
Key Switch: This switch which serves as a master power switch.

When the system is turned on the key may not be removed. If the

system is turned off the key may be removed.

Indicators

(see Figure 2)

Multi Function Display: This is a back-lit liquid crystal display. It

provides information to the operator regarding water quality, system

options, etc.
There are six individual LED's to indicate the following conditions:
(See Front View drawing)
On: Indicates when the system is on.
Overload: Indicates that the system has shut down due to an over-

load condition on one of the outputs.
Low Quality: Indicates that the quality of the water is below the

setpoint.
Tank Full: Indicates when the system is shut down due to a full stor-

age tank. The system will only shut down in the tank feed mode
Pretreatment Interlock: Indicates when the system is shut down

due to external pretreatment equipment.
Low-pressure: Indicates that the system has shut down due to low

pump feed pressure.

Operation

The key switch must be in the ON position (see Figure 2).

Contrast Adjustment

Press the up or down arrow when the home screen is displayed to

increase or decrease the contrast of the display.

Operation Screen

When the Start/Stop button is pressed the inlet valve will open.

After a 12 second delay the pump will start. The system will operate

according to the information stored in memory. The product water

conductivity is displayed in the large numbers at the top center of the

display. The temperature is displayed as degrees Celsius in the top

right corner of the display. The mode of operation is displayed below

the product water quality. Flush time information or pump run hours

are displayed on the bottom of the display.

Configuration Screen

Press the SELECT button to view the configuration screen. The

software revision level is displayed in the upper right corner of this

screen. While the configuration screen is displayed, the SELECT

button moves the highlight cursor to the next field. The up and down

arrows change the value of the highlighted field. The ACCEPT button

saves all of the values and brings up the timer screen. The RESET

button discards all changes and brings up the timer screen. If no

input is detected for a continuous 30 seconds, the controller will

discard all changes and return to the operation screen. An asterisk

appears next to a field whenever the value of the field equals the

value stored in memory. The configuration screen contains the fol-

lowing field with their options:
Mode: (direct feed, tank feed, and standby)
Low Quality: (2-200 micromhos) This is the set point for the diverter

valve. When the product water conductivity is equal to or greater

than value selected, the diverter valve output will be energized and

the low quality LED will turn on.
Autostart: (on/off) if “on” is selected, the system will automatically

restart after a power loss. If "off" is selected, the unit will not restart

after a power loss.
Low-pressure Retry: (0-10) This is the number of times the system

will attempt to restart after a low-pressure shutdown.
Low-pressure Delay: (15-90 seconds in 15 second increments)

This is the amount of time between attempts to restart after a low-

pressure shutdown.
Autoflush: (0-10 minutes) This is the length of the flush cycle. The

system will flush for this amount of time every hour in tank feed and

standby modes.
Inlet Delay Time: (10,30,60,120,300,600 seconds) This is the

amount of time that the inlet valve stays open after the pump turns

off.
Auxiliary Output Mode: This selects whether the auxiliary output

should be used for a diverter valve (default) or an alarm output.

Noted in the configuration menu as “Aux. Out”
Low Water Quality Alarm Delay: (0,5,10,30,60, 120,300,600 sec-

onds) This selects the delay between the detection of a low quality

water condition and the activation of the auxiliary output. This only

applies if the auxiliary output is configured as an alarm output. Noted

in the menu as “L/Q Alarm Delay”

Timer Screen

Pressing either the ACCEPT or the RESET button from the configu-

ration screen brings up the timer screen. The controller has three

timers (hour meters). Two are user resetable and one is not. All of

these timers count up when the pump is running. The two user rese-

table meters are labeled PREFILTER and MEMBRANE. Pressing the

reset button when either of these timers are highlighted will reset the

timer to zero. The SELECT button moves the highlight cursor to the

next timer. Press Accept while the membrane meter is highlighted to

exit and return to the operation screen.

Calibration Screen

This screen is used to calibrate the conductivity and temperature.

Press ACCEPT and RESET at the same time to bring up this screen.

The temperature and conductivity fields on the last two lines of the

display can be adjusted using the up and down arrows. Use the

arrow keys to input the correct temperature and then press the

ACCEPT button. The conductivity will now be highlighted. Use the

arrow keys to input the correct conductivity and press the ACCEPT

button. Always calibrate the temperature first. (Note: the new values

are only saved when the ACCEPT button is pressed while the field is

highlighted.) When the desired values are entered press the RESET

button to return to the operation screen. You can only enter the cali-

bration screen if the conductivity and temperature readings