Watts SD-3 User Manual

Model sd3, Sizes, 8 – 10mm)

Advertising
background image

IS-SD3

Model SD3

Backflow Preventors for Carbonated Beverage Machines

Installation Instructions

Sizes:

1

4

" –

3

8

" (8 – 10mm)

strainer included

Purpose

The Watts SD3 is a dual check with atmospheric

port designed for the protection of the water

supply from carbon dioxide gas and carbonated

water. These substances can flow from post-mix

beverage systems and are very acidic. If the

acidic water comes in contact with copper tub-

ing or copper pipe, it will cause the leaching of

copper salts into the water supply. The dissolved

copper if ingested can
cause nausea, abdominal pain, and in some

cases vomiting. The SD3 prevents the reverse

flow of potentially contaminated water back into

the potable water supply. In the event the sec-

ond check valve becomes fouled, the vent port

is opened to atmospheric and water and or CO2

gas from the downstream piping is discharged.

Installation

Before installing, flush out pipe lines to remove

scale and other foreign matter. The valve can be

installed horizontally or vertically (flow up or down).

Install the valve in the line with the arrow on the

valve body pointing in the direction of flow.

Connect a vent discharge line to the vent outlet of

the SD3 and vent to a safe place of disposal with

adequate ventilation. The valve should be installed

such that the strainer and the valve are accessible

for service and maintenance.

The valve should not be installed where water dis-

charge from the vent could cause damage to the

surrounding equipment or property. In addition, the

device should not be installed inside a wall or a

concealed location. Copper tubing shall not be

used on the downstream side of the backflow pre-

venter used in carbonated systems. Copper tub-

ing can be used downstream for non carbonated

systems such as coffee makers.

Applications

The Watts SD3 is recommended for use on

Carbonated Beverage Equipment and dispens-

ing equipment for tea and coffee.

Maintenance

Annual inspection is required of the strainer and

the backflow preventer to insure proper opera-

tion of the device.

Temperature and Pressure

Maximum Pressure - 150psi. (10.3 bar)

Maximum Temperature - 130°F. (54ºC)

Repair Kit

Kit consists of First and Second Check assem-

blies complete.

NOTICE

WARNING

!

Read this Manual BEFORE using this

equipment.

Failure to read and follow all safety

and use information can result in

death, serious personal injury, property

damage, or damage to the equipment.

Keep this Manual for future reference.

Advertising