VI. APPENDIX

The following tables are intended as a guide to determining the flow rates for the R14
series RO systems. All flows are in gallons per minute (GPM).

Nominal flows for systems without reject recycle

and a feed water Silt Density Index less than 3.

R14-02 R14-03 R14-04 R14-05 R14-06

Product 2.5

3.75

5 6.25

7.5

Reject

6.1

5.9

5

4.7

4.6

Nominal flows for systems with reject recycle

and a feed water Silt Density Index less than 3.

R14-02 R14-03 R14-04 R14-05 R14-06

Product 2.5

3.75

5 6.25

7.5

Reject

2.5

3.75 1.7 2.1 2.5

Reject

Recycle

3.6 2.2 3.3 2.6 2.1


Nominal flows for systems without reject recycle

and a feed water Silt Density Index of 3 to less than 5.

R14-02 R14-03 R14-04 R14-05 R14-06

Product 2.3 3.5 4.3 5.2 6.3
Reject

6.6 6.5 5.3 4.8 4.4

Nominal flows for systems with reject recycle

and a feed water Silt Density Index of 3 to less than 5.

R14-02 R14-03 R14-04 R14-05 R14-06

Product 2.3 3.5 4.3 5.2 6.3
Reject

2.3 3.5 1.4 1.7 2.1

Reject

Recycle

4.3 3 3.9 3.1 2.3