Watts TP300-DR User Manual

Trap primer & distribution unit tp300-dr, Flow chart

Advertising
background image

ES-WD-TP300-DR USA 1407 TP300-DR

Tag:

SPECIFICATION:

Watts Drainage TP300-DR pressure drop activated lead free*brass trap primer with EPDM seals, integral

air gap, and 1/2” sweat or NPT threaded connections. Operating pressure 25 psi - 125 psi. Tested and approved in

conformance with ASSE Standard 1018. Specify Model TP-300-DU-DR for Distribution Unit.

Trap Primer & Distribution Unit

TP300-DR

Flow Chart

INLET PRESSURE

25

50

75

100

125

*GPM

1.1

1.6

2.0

2.3

2.4

*LPM

4.2

6.1

7.6

8.7

9.1

*Minimum cold flow required for proper trap priming.

Model TP300T-DR

Model TP300S-DR

Model TP300 -DU-DR

Upper Disc Seal (1)

Supply

Valve Disc (2)
One Way Seal (3)

Lower Disc Seal (4)

Air Chamber (5)

To Trap

1 1/4

[32 mm]

1 1/4

[32 mm]

4 5/16

[110 mm]

4 1/4

[107 mm]

TP300T

Weight: 1.02 Lbs / .46 Kgs

TP300S

Weight: .95 Lbs / .43 Kgs

B

A

Model TP300T

Model TP300S

1 1/4

[32 mm]

1 1/4

[32 mm]

4 5/16

[110 mm]

4 1/4

[107 mm]

TP300T

Weight: 1.02 Lbs / .46 Kgs

TP300S

Weight: .95 Lbs / .43 Kgs

A

B

1

2 " Compression

4 Places

1

2 " NPT

B

A

MODEL

SIZE (DN)

DIMENSIONS

A

B

in.

mm

in.

mm

in.

mm

TP300T-DR

1

2

15

4

5

16

110

1

1

4

32

TP300S-DR

1

2

15

4

1

4

107

1

1

4

32

TP300-DU-DR

1

2

15

3

1

8

79

2

13

16

71

Threaded

Sweat

*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.

Advertising