Watts F1115-3 User Manual

Pressure reducing control valve, Hydraulic check feature, Lassic

Advertising
background image

X – Isolation Cocks

FC – Flo-Clean Strainer

Y – Y-Strainer (Replaces Flo-Clean)

ACS – Adjustable Closing Speed

(Replaces Fixed Orifice)

AOS – Adjustable Opening Speed

P – Position Indicator

L – Limit Switch

8550 Hansen Road

Houston, Texas 77075

(Ph) 713.943.0688

(Fx) 713.944.9445

www.watts.com

06/08

C

lassiC

s

eries

Standard Components

Options & Accessories

(3)

(3)

(3)

(2)

(2)

(1)

(1)

Standard 3” & Smaller

Standard 4” & Larger

Optional All Sizes

(3)

(2)

(1)

Schematics

Throttles to reduce high upstream pressure to

constant lower downstream pressure

P/L

X

X

X

X

1

Y/FC

2

CLOSES VALVE

OPENS VALVE

FLOW

3

4

3

(AOS)

F115-3 (Globe)

F1115-3 (Angle)

Operations

Hydraulic Check Feature prevents flow reversal

Reducing set-point is adjustable

PRESSURE REDUCING CONTROL VALVE

with

HYDRAULIC CHECK FEATURE

The Watts ACV Combination Pressure Reducing and Check Valve is designed to automatically reduce a

fluctuating higher upstream pressure to a constant lower downstream pressure, and close drip-tight when

downstream pressure becomes greater than upstream pressure.

It is controlled by a normally open, pressure reducing pilot designed to: 1) Open (allowing fluid out of the

main valve cover chamber) when downstream pressure is below the adjustable setpoint, and 2) Close

(allowing fluid to fill the main valve cover chamber) when downstream pressure is above the adjustable

setpoint. A decrease in downstream pressure causes the valve to modulate toward an open position, raising

downstream pressure. An increase in downstream pressure causes the valve to modulate toward a closed

position, lowering downstream pressure.

If downstream pressure becomes greater than upstream pressure, downstream pressure is admitted to the

main valve cover chamber, closing the valve and preventing reversal of flow. Normal pressure reducing

operation resumes when upstream pressure exceeds downstream pressure.

1 – Main Valve (Single Chamber)

2 – Pressure Reducing Control

3 – Check Valve

4 – Fixed Orifice

Advertising
This manual is related to the following products: